Heat Shrinkable Joints Upto 66Kv

 

Thenergie is committed to provide the highest quality power cable accessories. The company with it's Thenergy trademark stands leader in Europe and overseas market. The most dedicated team of design engineers, with over three decades of practical experience in cable jointing & terminating MV cables ensures that we stay at the forefront of the modern technology using most advanced materials & design concept

 

 

 

 

 

 

 

Straight Through Joint Suitable for 11Kv 3 Core PILC Cable

Item Code: CPS-1112

Owing to our expertise in this domain, we have been able to provide the customers with a comprehensive assortment of Straight Through Joint Suitable for 11 KV 3 Core PILC Cables UMAX -12 KV. Developed at par with the international quality standards,the range is highly suitable for 11 KV 3 Core PILC cables.

 

Offered in varied sizes & calibrations, the range is acknowledged for the following attributes:

 

  • Safe usage
  • Easy handling
  • Shock resistance
  • Easy installation


Electrical Specifications:

Test

Requirement

Typical Value

A.C. Dry Withstand Voltage

50 KV/1 Minute

Pass

D.C. Voltage Withstand Test

96 KV/15 Minute

Pass

Lightening Impulse withstand Voltage

125 KV

> 125 KV


Ordering Information:

Cable Size (Sq mm)

Kit Code 11 KV

16-35

CPS-11

50-95

CPS-12

120-185

CPS-13

240-400

CPS-14

500-630

CPS-15

 

 

 

 

 

Straight Through Joints Suitable for PVC/ XLPE/ PILC Cables

 

Electrical Performance

Tests

1.1KV

3.3KV System

A.C. Voltage Withstand

3.5 KV / 5 Minute

5KV/5 Minute

D.C. Voltage Withstand

15 KV /15 Minute

20 KV/15 Minute

 

 

 

 

Ordering Information

 

Cable Size (Sq mm)

Kit Code 
1.1 KV

Kit Code 
3.3 KV

4 x 1.5-6

CXLT -1

CXLT -11

4 x 1.0-16

CXLT -2

CXLT -12

4 x 25-50

CXLT -3

CXLT -13

4 x 70-150

CXLT -4

CXLT -14

4 x 185-400

CXLT -5

CXLT -15

 

 

 

 

Straight Through Joints Suitable for 3 core XLPE/ EPR/ PVC

 

Item Code: CXS-E-1236KV

We are established manufacturers of heat shrinkable straight through joints for XLPE/ PVC cables from 1.1 KV tO 36 KV, heat shrinkable jointing kits and cable jointing kits. The range of heat shrinkable jointing kits is comprehensive and highly suitable for XLPE and PVC insulated cables of different voltages. Fully tested and qualified to industry standards, these cable jointing kits feature heat activated seals and offer superior performance.

 

Electrical Performance

Test Requirement

12KV 
(6.6/6.6KV,6.36/11KV)

15-24KV
(8.7/15KV,11/11KV,12.7/22KV)

36KV
(19/33KV)

A.C. Withstand, 1 Minute

35 KV

50KV

75KV

D.C. Withstand, 15 Minute

48KV

96KV

144KV

Discharge Extintion Voltage (<5Pc)

12.7 KV(Min)

25.4KV(Min)

38KV(Min)

Impulse Withstand (Crest KV)

75KV(Min)

125KV

170KV(Min)

Continuous Current Rating

As Per Cable

As Per Cable

As Per Cable

 

 

 

Electrical Performance

Tests

1.1KV

3.3KV System

A.C. Voltage Withstand

3.5 KV / 5 Minute

5KV/5 Minute

D.C. Voltage Withstand

15 KV /15 Minute

20 KV/15 Minute

 
 
 
 

Straight Through Joints for 33KV 3 Core Screened PILC Cable

 

Heat Shrinkable Terminations Suitable for 3 Core Paper Insulated Lead Covered MIND Cable for 24 KV

Test

Requirement

Typical Value

A.C. Dry Withstand Voltage

50 KV/1 Minute

Pass

D.C. Voltage Withstand Test

96 KV/15 Minute

Pass

Lightening Impulse withstand Voltage

125 KV

> 125 KV

 

 

 

Ordering Information

22 KV (24 KV)

33 KV (36 KV)

Cable Size (Sq mm)

Kit Code

Cable Size (Sq mm)

Kit Code

25-50

CPS-21

35-70

CPS-31

70-120

CPS-22

95-150

CPS-32

150-240

CPS-23

185-300

CPS-33

300-500

CPS-24

400

CPS-34

 
 
 
 

Transition Joints Suitable 3 Core XLPE/PILC cable upto 12 kV

 

 

Test

Requirement

Typical Value

A.C. Dry Withstand Voltage

50 KV/1 Minute

Pass

D.C. Voltage Withstand Test

96 KV/15 Minute

Pass

Lightening Impulse withstand Voltage

125 KV

> 125 KV

 


                                                                                          ODERING INFORMATION 

 

CABLE SIZE
(Sq. mm)

Kit Code 11 KV

 

16-35

CPS-11

 

50-95

CPS-12

 

120-185

CPS-13

 

240-400

CPS-14

 

500-600

CPS-15

 
 

 

 

 

 

Transition Through Joint Suitable 3 Core XLE/PILC Cable 36kV

 

Test

Requirement

Typical Value

A.C. Dry Withstand Voltage

50 KV/1 Minute

Pass

D.C. Voltage Withstand Test

96 KV/15 Minute

Pass

Lightening Impulse withstand Voltage

125 KV

> 125 KV

 

 

Heat Shinkable Terminations Suitable for 3 Core Paper Insulated Lead Covered MIND Cable for 24 KV

Test

Requirement

Typical Value

 

 

Ordering Information

15-24 KV System

36 KV System

Cable Size (Sq mm)

Kit Code

Cable Size (Sq mm)

Kit Code

25-50

CTJ-21

35-70

CTJ-31

70-95

CTJ-22

95-150

CTJ-32

120-150

CTJ-23

185-300

CTJ-33

185-300

CTJ-24

400

CTJ-34

400-500

CTJ-25

-

-

 
 
 

 

Joints Suitable for Single Core XLPE/EPR/PVC Insulated Cable

 

Heat Shrinkable Straight Through Joints Suitable for Single Core XLPE/EPR/PVC Insulated Cables for up to 36kv

 

Test

12 KV System

15-24KV System

36 KV

AC Dry Withstand voltage

35KV/1 minute

50KV/1 Minute

75KV/1 Minute

DC Withstand 30 Minute

48 KV

96 KV

144KV

Lightening Impulse withstand Voltage

75 KV

125 KV

170 KV

Partial Discharge

12.7 Kv < 5 Pc

25 Kv < 5 Pc

38 Kv < 5 Pc

 


ORDERING INFORMATIONS
12 KV SYSTEM

 

CABLE SIZE
(Sq. mm)

Indoor Kit Code

 

16-50

CXES-11

 

70-120

CXES-12

 

150-300

CXES-13

 

400-630

CXES-14

 

800-1000

CXES-15

 
 

 

 

CABLE SIZE
(Sq. mm)

Outdoor Kit Code

 

16-50

CXOS-11

 

70-120

CXOS-12

 

150-300

CXOS-13

 

400-630

CXOS-14

 

800-1000

CXES-15

 
 


24 KV INDOOR TERMINATIONS

 

CABLE SIZE
(Sq. mm)

Indoor Kit Code

 

16-50

CXES-21

 

70-150

CXES-22

 

185-300

CXES-23

 

400-630

CXES-24

 

800-1000

CXES-25

 
 

 

 

CABLE SIZE
(Sq. mm)

Outdoor Kit Code

 

16-50

CXOS-21

 

70-150

CXOS-22

 

185-300

CXOS-23

 

400-630

CXOS-24

 

800-1000

CXES-25